How to get it right: Bolting timbers together correctly

If you are doubling up floor joists, creating trimmers or trimming joists around stairs and chimneys they all need connecting properly so that they can act as a single unit.

Whilst timber floors and their connection details should be designed by a competent person, the Eurocode 5 Span Tables (4th edition) published by TRADA offers good advice on typical connection details for solid timbers, such as the sizes of nails or bolts and their location and centres. Some of the key parts of this guidance document in relation to connecting trimmers or trimming joists are summarised below:

The nail specification used is dependent on the thickness of the timbers being used:

The minimum bolt specification to be used is:

It may be possible to use other types of fasteners for which capacities have been obtained experimentally and declared by manufacturers with third party certification e.g. dog tooth connectors.

Fixing can be either along the centreline or staggered as shown in the diagrams below:

Nails must be a minimum of15 times their diameter from the joist end and at least 5 times their diameter from the top and bottom.

Bolts must be aminimum of7 times their diameter or 80mm from the joist end and at least 4 times their diameter from the top and bottom.

Images courtesy of Eurocode 5Span Tables (4th edition) published by TRADA

Double member trimmers and trimming joists should be fixed in line with a minimum of two nails or two bolts at 1/3 span positions. Furthermore, as a minimum, the fixing centres (S) for double member trimmers and trimming joists should be at centres of no more than twice the joist spacing (up to a maximum of 1200mm). However, required fixing centres vary according to the total length and load on the joists.

These tables have been taken fromEurocode 5 Span Tables (4th edition) published by TRADAto illustrate how the above works and should be consulted for any other timber sizes not shown.

No notching or drilling of trimmers or trimming joists should be carried out unless proven by calculation, other than to accommodate the flanges of joist hangers.

Further reading

Eurocode 5 Span Tables 4th edition for solid timber members in floors, ceilings and roofs for dwellings, August 2014, BM Trada, ISBN: 978-1-909594-14-2, Published by BM TRADA


Disclaimer:

Every care has been taken to ensure that the above content is correct at the time of publication. Any reliance on the content should be verified by the dutyholder(s) and their professional advisers. It is the responsibility of the dutyholder(s) and/or person carrying out the work to ensure compliance with the relevant building regulations and associated legislation.

This content is given in good faith by LABC. It is not definitive, and compliance will be a matter for the relevant building control authority to decide as the enforcing body for the building regulations, and ultimately for the appropriate tribunal or court to determine.

TT_8.1

This article was originally published on the LABC website on 07/08/2018. View the original article.